| SIPLUS ET200S EM 2RO DC24V-AC230V/5A -25 ... +70 DEGREES C BASED ON 6ES7132-4HB01-0AB0 5 PIECES PER PACKAGING UNIT . ELECTRON. MODULES FOR ET 200S, 2 DO RELAY 24V DC - 230V AC/5A,15 MM WIDTH FIRST-UP SIGNAL WITH LED SF (GROUP FAULT), |
|
Supply voltage |
Load voltage L+ |
Rated value (DC) | 24 V; From power module |
Reverse polarity protection | Yes |
Input current |
from load voltage L+ (without load), max. | 30 mA |
from backplane bus 3.3 V DC, max. | 10 mA |
Power losses |
Power loss, typ. | 0.6 W |
Address area |
Address space per module |
with packing | 2 bit |
without packing | 1 byte |
Digital outputs |
Number/binary outputs | 2 |
Functionality/short-circuit strength | No; external fuse, max. 6 A quick-acting |
Limitation of inductive shutdown voltage to | No |
Controlling a digital input | Yes |
Output current |
for signal "1" rated value | 5 A |
for signal "1" minimum load current | 8 mA |
Parallel switching of 2 outputs |
for increased power | No |
for redundant control of a load | No |
Switching frequency |
with resistive load, max. | 2 Hz |
with inductive load, max. | 0.5 Hz |
on lamp load, max. | 2 Hz |
Relay outputs |
Switching capacity of contacts |
Thermal continuous current, max. | 5 A |
Cable length |
Cable length, shielded, max. | 1000 m |
Cable length unshielded, max. | 600 m |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information |
Substitute values connectable | Yes; 0/1 |
Diagnostic messages |
Diagnostic functions | No |
Diagnostics indication LED |
Status indicator digital output (green) | Yes |
Parameter |
Remark | 3 bytes |
Behavior on CPU/Master STOP, channel-wise | Substitute a value/keep last value |
Galvanic isolation |
Galvanic isolation digital outputs |
between the channels | Yes |
between the channels and the backplane bus | Yes |
between the channels and the load voltage L+ | Yes |
Isolation |
tested with |
Channels against backplane bus and load voltage L+ | 1500 V AC |
Load voltage L+ against backplane bus | 500 V DC |
Ambient conditions |
Extended ambient conditions |
Relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity |
with condensation / maximum | 100 %; , incl. condensation / frost permitted (no commissioning under condensation conditions) |
Resistance |
to biologically active substances / conformity with EN 60721-3-3 | Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! |
to chemically active substances / conformity with EN 60721-3-3 | Yes; , Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
to mechanically active substances / conformity with EN 60721-3-3 | Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions |
Width | 15 mm |
Height | 81 mm |
Depth | 52 mm |
Weight |
Weight, approx. | 50 g |
Status | Mar 12, 2012 |