| SIPLUS S7-400 PS407 10A REDUNDANT FOR MEDIAL STRESS BASED ON 6ES7407-0KR02-0AA0 |
|
Supply voltage |
Rated value, 110 V DC | Yes; Rated value 120 V DC |
Rated value, 230 V DC | Yes |
permissible range, lower limit (DC) | 88 V |
permissible range, upper limit (DC) | 300 V |
Rated value, 120 V AC | Yes |
Rated value, 230 V AC | Yes |
Line frequency |
Rated value 50 Hz | Yes |
Rated value 60 Hz | Yes |
permissible range, lower limit | 47 Hz |
permissible range, upper limit | 63 Hz |
Mains buffering |
Mains/voltage failure stored energy time | 20 ms |
Mains buffering according to NAMUR recommendation | Yes |
Input current |
Rated value at 110 V DC | 1 A; at 120 V DC |
Rated value at 230 V DC | 0.5 A |
Rated value at 120 V AC | 0.9 A |
Rated value at 230 V AC | 0.5 A |
Inrush current, max. | 63 A; Full width at half maximum 1 ms |
Output voltage |
Rated value, 5 V DC | Yes |
Rated value, 24 V DC | Yes |
Output current |
for backplane bus (5 V DC), max. | 10 A; no base load required |
for backplane bus (24 V DC), max. | 1 A; idling-proof |
Short-circuit protection | Yes |
Power |
Power consumption, typ. | 95 W |
Power losses |
Power loss, typ. | 20 W |
Backup battery |
Backup battery | |
Backup battery (optional) | Yes; 2 x lithium AA; 3.6 V/2.3 Ah |
Galvanic isolation |
primary/secondary | Yes |
EMC |
Compliance with line harmonic distortion limits |
Observance of line harmonic distortion acc. to IEC 61000-3-2, IEC 61000-3-3 | Yes |
Ambient conditions |
Extended ambient conditions |
Relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity |
with condensation / maximum | 100 % |
Resistance |
to biologically active substances / conformity with EN 60721-3-3 | Yes |
to chemically active substances / conformity with EN 60721-3-3 | Yes; , Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
to mechanically active substances / conformity with EN 60721-3-3 | Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Mechanical and climatic conditions during operation |
Climatic conditions in operation |
Temperature |
Min. | 0 °C; = Tmin |
max. | 60 °C; = Tmax |
Degree and class of protection |
Protection class | 1; with protective conductor |
Connection method |
Connecting cables/cross sections | 3 x 1.5 mm2, solid or stranded wire with end sleeve, external diameter 3 to 9 mm |
Dimensions |
Width | 50 mm |
Height | 290 mm |
Depth | 217 mm |
Required slots | 2 |
Weight |
Weight, approx. | 1200 g |
Status | Dec 19, 2011 |