| SIPLUS S7-400 IF964-DP -25 ... +70 DEGREES C WITH CONFORMAL COATING BASED ON 6ES7964-2AA04-0AB0 . INTERFACE MODULE DP MASTER |
|
Input current |
from CPU, max. | 150 mA; Current consumption from S7-400 bus: The module uses no current at 24 V, it provides this voltage only at the DP interface. Total current consumption of the components connected to the DP interface, but maximum 150 mA. Current carrying capacity of the isolated 5 V (P5ext) maximum 90 mA, current carrying capacity of the 24 V maximum 150 mA. |
Power losses |
Power loss, typ. | 1 W |
Interfaces |
PROFIBUS DP |
Cable length, max. | 1200 m; At 9.6 kbit/s: max. 1200 m; at 12 Mbit/s: max. 100 m |
1st interface |
Physics | RS 485 |
Isolated | Yes |
Functionality |
DP master | Yes; Default setting |
DP slave | Yes |
DP master |
Services |
PG/OP communication | Yes |
Equidistance mode support | Yes |
SYNC/FREEZE | Yes |
Direct data exchange (slave-to-slave communication) | Yes |
Transmission rate, max. | 12 Mbit/s |
Transmission rate, min. | 9.6 kbit/s |
Number of DP slaves, max. | 125; depending on the CPU used |
Address area |
Inputs, max. | device-dependent |
Outputs, max. | device-dependent |
User data per DP slave |
Inputs, max. | 244 byte |
Outputs, max. | 244 byte |
Communication functions |
Number of connections |
overall | device-dependent |
Ambient conditions |
Extended ambient conditions |
Relative to ambient temperature-atmospheric pressure-installation altitude | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity |
with condensation / maximum | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
Resistance |
to biologically active substances / conformity with EN 60721-3-3 | Yes; , Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
to chemically active substances / conformity with EN 60721-3-3 | Yes; , Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
to mechanically active substances / conformity with EN 60721-3-3 | Yes; , Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Mechanical and climatic conditions during operation |
Climatic conditions in operation |
Temperature |
Min. | -25 °C; = Tmin |
max. | 70 °C; = Tmax |
Dimensions |
Width | 26 mm |
Height | 54 mm |
Depth | 130 mm |
Weight |
Weight, approx. | 65 g |
Status | Mar 12, 2012 |