193-EC1GG - 193-EC1, E3 Electronic Motor Protection Relay, 2 Inputs 1 Output, Direct Contactor Mount, 42-210A - Quad Industry GmbH
|
Plan View Drawings (3D Format)
Catalog Number | Page | AutoCAD® DWG | DXF | Adobe® PDF | Windows Metafile |
---|---|---|---|---|---|
193-EC1GG | ABOLF070.DWG | ABOLF070.DXF | ABOLF070.PDF | ABOLF070.WMF |
3 View Dimension Drawings (3D Format) | |||||||||||||
|
Short Circuit Ratings |
Operational Rating | Dual Element Time Delay Fuses | Circuit Breakers | Rating Reference | File Ref: UL | File Ref: CSA | Comments | ||||||||
SCCR [kA] | Max Fuse Size [A] | Fuse Class | CB Type | UL CMC Type | Catalog Numbers | SCCR [kA] | SCCR [kA] | SCCR [kA] | SCCR [kA] | |||||
600V | 480V | 480Y/277V | 600V | 600Y/347V | ||||||||||
FLC: 42..210 Amps | 100 | 400 | J | UL 508 Manual Motor Controller | -- | -- | -- | -- | -- | -- | Instruction Sheet | E14840 | cULus | For Use with 100-D210 or larger |
FLC: 42..210 Amps | 100 | 500 | J | UL 508 Type E Comb. Motor Controller | -- | -- | -- | -- | -- | -- | Instruction Sheet | E14840 | cULus | For Use with 100-D300 or larger |
FLC: 42..210 Amps | -- | -- | -- | UL 489 MCCB | C | 140U-J6D3-D25 | 65 | 65 | 30 | 25 | Instruction Sheet | E14840 | LR1234 | For Use with 100-D210 or larger |
FLC: 42..210 Amps | -- | -- | -- | UL 489 MCCB | C | 140U-K6D3-D40 | 65 | 65 | 30 | 30 | Instruction Sheet | E14840 | LR1234 | For Use with 100-D250 or larger |
FLC: 42..210 Amps | -- | -- | -- | UL 489 MCP | D | 140M-J8P-D25 | 65 | 65 | 30 | 30 | Instruction Sheet | E14840 | LR1234 | For Use with 100-D210 or larger |
FLC: 42..210 Amps | -- | -- | -- | UL 489 MCP | D | 140M-K8P-D40 | 65 | 65 | 30 | 30 | Instruction Sheet | E14840 | LR1234 | For Use with 100-D250 or larger |
193EC1GG
193EC-1GG
193-EC1GG
193EC 1GG
193 EC1GG