193-EC1CD - 193-EC1, E3 Electronic Motor Protection Relay, 2 Inputs 1 Output, Direct Contactor Mount, 5-25A - Quad Industry GmbH
|
Plan View Drawings (3D Format)
Catalog Number | Page | AutoCAD® DWG | DXF | Adobe® PDF | Windows Metafile |
---|---|---|---|---|---|
193-EC1CD | ABOLF040.DWG | ABOLF040.DXF | ABOLF040.PDF | ABOLF040.WMF |
3 View Dimension Drawings (3D Format) | |||||||||||||
|
Short Circuit Ratings |
Operational Rating | Dual Element Time Delay Fuses | Circuit Breakers | Rating Reference | File Ref: UL | File Ref: CSA | Comments | ||||||||
SCCR [kA] | Max Fuse Size [A] | Fuse Class | CB Type | UL CMC Type | Catalog Numbers | SCCR [kA] | SCCR [kA] | SCCR [kA] | SCCR [kA] | |||||
600V | 480V | 480Y/277V | 600V | 600Y/347V | ||||||||||
FLC: 5.0…25 Amps | 100 | 50 | CC,J | UL 508 Manual Motor Controller | -- | -- | -- | -- | -- | -- | Instruction Sheet | E14840 | cULus | For Use with 100-C30 or larger |
FLC: 5.0…25 Amps | 100 | 70 | CC,J | -- | -- | -- | -- | -- | -- | -- | Instruction Sheet | E14840 | cULus | For use with 100-C43 |
FLC: 5.0…25 Amps | -- | -- | -- | UL 508 Type E Comb. Motor Controller | E (3 Comp) | 140M-D8N-C25 | -- | 65 | -- | -- | Instruction Sheet | E125316 | cULus | For Use with 100-C30 or larger |
FLC: 5.0…25 Amps | -- | -- | -- | UL 508 Type E Comb. Motor Controller | E (3 Comp) | 140M-F8N-C25 | -- | 65 | -- | 30 | Instruction Sheet | E125316 | cULus | For Use with 100-C30 or larger |
FLC: 5.0…25 Amps | -- | -- | -- | UL 489 MCCB | C | 140U-H6C3-C50 | 50 | 50 | -- | 25 | Instruction Sheet | E14840 | cULus | -- |
FLC: 5.0…25 Amps | -- | -- | -- | UL 489 MCP | D | 140M-H8P-C50 | 65 | 65 | 30 | 30 | Instruction Sheet | E14840 | cULus | -- |
193EC1CD
193EC-1CD
193-EC1CD
193EC 1CD
193 EC1CD
Назад в раздел
|
Quad Industry GmbH
GER + 49 (30) 994-049-88 E-mail: sales@quad-industry.com |